whatsapp
Brand DELTA UPS System On Line UPS Delta Make 10 KVA 3:1 Phase On-Line UPS (EH Series)

Delta Make 10 KVA 3:1 Phase On-Line UPS (EH Series)

Ultron EH-10kVA

UPS System On Line UPS

Price: 128620

MRP 293112 You save 164492

Power Reliability with the Best Total Cost of Ownership

The Ultron EH series is an online double-conversion 3p-1p UPS which provides reliable power protection for IT rooms, SMBs, telecommunications, banking, medical facilities and industry. Supported with DSP based technology, it offers rapid computation capabilities that enhance system stability and provide precise voltage to load. The Ultron EH series offers many superior features including N+X parallel redundancy and a built-in manual bypass switch to guarantee higher availability and reliability for protecting your critical loads.

About Delta EH Series

  • The Delta Ultron EH series is a true online, double-conversion UPS. It is a proven power solution for IT rooms, telecommunications, banking, medical facilities, laboratories, and other settings in which mission critical applications cannot be disrupted.
  • True online double-conversion UPS technology isolates the output power and protects it from input anomalies. The dual input design of the Ultron EH series provides enhanced availability by accommodating different power supply sources. By accepting a wide input voltage range, EH series UPS units reduce probability of battery discharge to prolong battery life. Even if the UPS is under maintenance, a continuous supply of power to the load can be maintained by the use of the built-in manual bypass.
  • When paired with the EH series' multi-connectivity interface, Delta's advanced management software supports analysis, remote UPS management and monitoring, remote shutdown event log tracking, and event alert management. System stability is further enhanced by the unit's simplified control circuit, and rapid computational capability is facilitated by the use of DPS-based technology.
  • For a modest initial investment, the double-conversion UPS series - EH provides both outstanding quality and one of the lowest costs of ownership for UPS systems within the 10-20 kVA range. To shrink the cost of operation even more, the units can be run in ECO mode for efficiency of up to 96%.
  • Applications:

  • Datacenter Telecom Industrial Network Security Banking Lab Medical Metro Retail

  • Reset default

    Features

    Ultron EH Series Features
    Assured Reliability
    True online double-conversion technology to completely isolate the output power from all input anomalies.
    DSP based technology to support rapid computation capability and a simplified control circuit for enhanced stability.
    Dual input design to allow different power supply sources for enhanced availability.
    Built-in manual bypass to ensure continuous power to the load even if the UPS fails.
    Cost of Ownership
    A wide input voltage range of up to 305~477V to reduce battery discharge probability and prolong battery life.
    ECO mode efficiency up to 96% to reduce operating cost.
    Small footprint to save space.
    Flexibility
    Parallel expansion and N+X redundancy up to 4 units without requiring additional cards or equipment.
    Additional charger and external charger box for flexible capacity expansion.
    Remote and local emergency power-off functions (EPO) to promptly manage the UPS when emergencies occur.
    Manageability
    Multi-connectivity interface to support remote UPS monitoring and management.
    Advanced management software to provide event alert management, remote shutdown event log tracking and analysis.
    Reliable battery management for better battery protection.

    Specification

    Output Specification
    Output Capacity (KVA )
    10 KVA
    Output Capacity (KW )
    8 KW
    Output Power Factor
    0.8 Power Factor
    Output Phase
    1 Phase
    Output Voltage
    400 Volt
    Other Output Voltage
    380 Or 415 Volt
    Efficiency at Full Load
    > 91 %
    Output Voltage Distortion
    <3 %
    Output Frequency (sync to mains)
    50/60Hz +/- 3 Hz
    Load Crest Factor
    3:1
    Output Waveform type
    Sine Wave
    Output Connections
    UPS Parallel Upto
    4 Nos.
    General Specifications
    Flexible Battery Option
    No
    Isolation Transformer
    Paralleling Options
    Yes
    Rack Mounting Kit
    Not Available
    Paralleling Kit for Synchronising
    Inclusive
    Input Specification
    Input Voltage
    400 Volt
    Other Input Voltage
    380 Or 415 Volt
    Input Phase
    3 Phase
    Other Input Phase
    1 Or Phase
    Input frequency
    50/60Hz +/- 3 Hz
    Input Voltage Range (Output Derated)
    208 - 304 Volt
    Input voltage range for main operations
    305 - 477 Volt
    Input frequency Range
    50 - 60 Hz
    Input Power Factor
    > 0.99
    Batteries & Runtime
    Battery DC Bus
    240 VDC
    Maximum Charger Capacity
    4 Amp.
    Battery Position Option
    External
    Battery Type Compatibility
    SMF / Flooded Batteries
    Approved Battery Capacity (AH)
    17 - 200 Amp.
    Communication & Management
    SNMP Management
    Optional
    Power Management Software
    Optional
    Interface Port(s)
    RS-232, USB
    Audible noise at 1 meter from surface of unit
    55 < Decibal
    Physical
    Maximum Height
    490 Mm
    Maximum Width
    200 Mm
    Maximum Depth
    490 Mm
    Net Weight
    26 Kg
    Environmental
    Operating Temperature
    0 - 40 °C
    Operating Relative Humidity
    5 - 95 % Rh
    Other Specifications
    Technology
    Double Conversion Online

    Documentation

    Item Catalogue
    Delta Make 10 KVA On-Line UPS (EH Series)
    pdf

    Options