Specification
Output Capacity (KVA )
20 KVA
Output Capacity (KW )
16 KW
Output Power Factor
0.8 Power Factor
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
> 88 %
Output Voltage Distortion
< 3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
Isolation Transformer
In-Built
Flexible Battery Option
Yes
Paralleling Kit for Synchronising
Optional
Other Input Voltage
380 Or 415 Volt
Input frequency
50 Or 60 Hz
Input frequency Range
45 - 65 Hz
Input Voltage Range (Output Derated)
190 - 520 Volt
Input voltage range for main operations
304 - 477 Volt
Input Connections
Hard Wire 5-wire (3PH + N + G)
Battery DC Bus
348 - 384 VDC
Battery Type Compatibility
SMF Battery
Maximum Charger Capacity
20 Amp.
Battery Position Option
External
Approved Battery Capacity (AH)
17 - 200 Amp.
Battery Circuit Breaker
In-Built
Communication & Management
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %