Specification
Output Capacity (KVA )
15 KVA
Output Capacity (KW )
12 KW
Output Power Factor
0.8 Power Factor
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
>99 %
Output Voltage Distortion
<3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Output Voltage THD
< 3% linear load and <5% non-linear load
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
Bypass
Built-in Maintenance Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
UPS Parallel Upto
In-Built
Other Input Voltage
380 - 415 Volt
Input frequency
50 Or 60 Hz
Input frequency Range
45 - 65 Hz
Input Voltage Range (Output Derated)
Input voltage range for main operations
304 - 477 Volt
Input Power Factor
>0.99 Power Factor
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input Protection
Circuit Breaker & Fuse
Input Short Circuit Current (Maximum)
10 kAmps.
Input Current (Maximum)
37 Amp.
Battery Position Option
External
Approved Battery Capacity (AH)
7 - 100 Amp.
Battery DC Bus
384 - 480 Vdc
Battery Type Compatibility
SMF Battery
Communication & Management
Control panel
Touch Screen LCD User Interface
Power Management Software
Optional
Interface Port(s)
E3M_ColdStart, E3M_parallel, E3S_TempSensor
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
60 Decibal
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %
Storage Temperature
-15 - 40 °C
Storage Relative Humidity
0 - 95 %
Online thermal dissipation
Approvals
CE, EAC, IEC 62040-1-1, IEC 62040-2, IEC 62040-3, IEC 62040-4, ISTA 2B, RCM, WEEE
Other Environmental Compliance
Compliant
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449