whatsapp
Brand EATON UPS System On Line UPS Eaton Make 1 KVA On-Line UPS

Eaton Make 1 KVA On-Line UPS

9145-1000IN

UPS System On Line UPS

Price:

MRP You save 0


Reset default

Specification

Output Specification
Output Capacity (KVA )
1 Kva
Output Capacity (KW )
0.8 Kw
Output Power Factor
0.99 Power Factor
Output Phase
1 Phase
Output Voltage
230 Volt
Other Output Voltage
220 Or 240 Volt
Efficiency at Full Load
>99 %
Output Voltage Distortion
<2 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Load Crest Factor
3:1
Output Voltage THD
<3 %
Transfer Time
<0 Ms
Output Waveform type
Sine Wave
Output Connections
3 Pin Indian Socket (04 Nos.)
Bypass
Internal Bypass (automatic & manual)
Overload Capacity
Optional
Input Specification
Input Voltage
230 Volt
Other Input Voltage
208 Or 240 Volt
Input Phase
1 Phase
Input frequency
50/60Hz +/- 3 Hz
Input Voltage Range (Output Derated)
110 - 300 Volt
Input voltage range for main operations
110 - 300 Volt
Input frequency Range
45 - 55 Hz
Input Power Factor
>0.99 None
Input Connections
3-Pin 6A Indian Socket
Batteries & Runtime
Battery DC Bus
24 - VDC
Maximum Charger Capacity
8 Amp.
Battery Position Option
External
Battery Type Compatibility
SMF Battery
Batteries Recharge Time upto 90%
<5 Hrs.
Approved Battery Capacity (AH)
9 - Amp.
Communication & Management
Control panel
Multi-function LCD status and control console
SNMP Management
In-Built
Power Management Software
In-Built
Interface Port(s)
DB-9 RS-232, Smart-Slot
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
<50 Decibal
Physical
Maximum Height
220 Mm
Maximum Width
140 Mm
Maximum Depth
400 Mm
Net Weight
13 Kg
Environmental
Operating Temperature
0 - 45 °C
Operating Relative Humidity
0 - 90 % Rh
Storage Temperature
-20 - +60 °C
Compliances
Compliance
IS 16242 (Part1): 2014
Approvals
IS 16242 (Part1): 2014
Other Environmental Compliance
IS 16242 (Part1): 2014
Other Specifications
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Surge Protection
Yes