Specification
Output Capacity (KVA )
10 Kva
Output Capacity (KW )
9 Kw
Output Power Factor
0.9 Power Factor
Other Output Voltage
208 Or Volt
Efficiency at Full Load
>94 %
Output Voltage Distortion
<1 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Output Waveform type
Sine Wave
Output Connections
Hard Wire 3 wire (1PH+N+G)
Bypass
Internal Bypass (automatic & manual)
Overload Capacity
150% for 1 minute 125% for 10 minutes
Flexible Battery Option
No
Isolation Transformer
Optional
Rack Mounting Kit
Not Available
Paralleling Kit for Synchronising
Optional
Other Input Voltage
208 Or 240 Volt
Input frequency
50/60Hz +/- 3 Hz
Input Voltage Range (Output Derated)
110 - 276 Volt
Input voltage range for main operations
160 - 276 Volt
Input frequency Range
45 - 55 Hz
Input Power Factor
>0.99 None
Input Connections
Hard Wire 3 wire (1PH+N+G)
Maximum Charger Capacity
4 Amp.
Battery Position Option
External
Battery Type Compatibility
SMF Battery
Batteries Recharge Time upto 90%
<5 Hrs.
Approved Battery Capacity (AH)
17 - 65 Amp.
Communication & Management
Control panel
Multi-function LCD status and control console
Power Management Software
In-Built
Interface Port(s)
DB-9 RS-232, Smart-Slot
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
<55 Decibal
Operating Temperature
0 - 40 °C
Operating Relative Humidity
20 - 90 % Rh
Technology
Double Conversion Online