Specification
Output Capacity (KVA )
300 KVA
Output Capacity (KW )
270 KW
Output Power Factor
0.9 Power Factor
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
> 94 %
Output Voltage Distortion
< 3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
+/- 0.1% for 50/60Hz Nominal
Output Voltage THD
< 3% linear load and <5% non-linear load
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
Bypass
Built-in Static Bypass
Overload Capacity
150% for 1 minute 125% for 10 minutes
Isolation Transformer
In-Built
Paralleling Kit for Synchronising
Not Available
Other Input Voltage
384 Or 415 Volt
Input frequency
50 Or 60 Hz
Input Connections
Hard Wire 5-wire (3PH + N + G)
Battery Position Option
External
Approved Battery Capacity (AH)
150 - 200 Amp.
Battery Circuit Breaker
Optional
Battery Type Compatibility
SMF Battery
Maximum Charger Capacity
55 Amp.
Communication & Management
Control panel
LCD Display
Power Management Software
Not Available
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
< 42 Decibal
Operating Temperature
0. - 55 °C
Operating Relative Humidity
0 - 95 %
Operating Elevation
0 1000
Storage Temperature
0 - 65 °C
Storage Relative Humidity
0 - 95 %
Storage Elevation
0 - 1000 Meters
Compliance
EN/IEC 62040-1, IEC 62040-2, IEC 62040-3, IEC 62040-4
Approvals
CE, EAC, IEC 62040-1-1, IEC 62040-2, IEC 62040-3, IEC 62040-4, ISTA 2B, RCM, WEEE
Other Environmental Compliance
Compliant
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449