Specification
Output Capacity (KVA )
30 KVA
Output Capacity (KW )
30 KW
Output Power Factor
1 Power Factor
Other Output Voltage
380 Or 415 Volt
Efficiency at Full Load
> 95 %
Output Voltage Distortion
< 3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
+/- 0.1% for 50/60Hz Nominal
Output Voltage THD
< 3% linear load and <5% non-linear load
Output Waveform type
Sine Wave
Output Connections
Hard Wire 5-wire (3PH + N + G)
UPS Parallel Upto
Not Available
Isolation Transformer
Optional
Paralleling Kit for Synchronising
Not Available
Other Input Voltage
380 Or 415 Volt
Input frequency
50 Or 60 Hz
Input frequency Range
45 - 65 Hz
Input Voltage Range (Output Derated)
190 - 520 Volt
Input voltage range for main operations
304 - 477 Volt
Input Connections
Hard Wire 5-wire (3PH + N + G)
Battery DC Bus
384 480 VDC
Battery Type Compatibility
SMF Battery
Battery Position Option
External
Approved Battery Capacity (AH)
26 - 150 Amp.
Battery Circuit Breaker
In-Built
Communication & Management
Power Management Software
Optional
Audible noise at 1 meter from surface of unit
< 60 Decibal
Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %
Technology